Skip to main content

FHSD8025-7-ULF

LaserSense 25 High Sensitivity Smoke Detector - UL & FM
  • UL approved to the latest UL268 7th edition
  • Ultra small low cost aspirating smoke detector for easy and discreet installation
  • High sensitivity provided by laser based forward light scatter for reliable early warning
  • Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
View all

At a glance

Description

LaserSense 25 is designed to provide very high sensitivity smoke detection in a small package.

ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.

The detector is designed to fit into a Docking Station. All sampling pipes and cables are connected to the Docking Station as a first fix operation leaving the detector to be fitted during the final commissioning phase if required. This ensures that detectors are less likely to be damaged during the installation.

Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.

Typical Applications

- Data storage units
- Prison cells
- Plant rooms
- Air conditioning units
- Equipment racks
- Computer rooms
- Heritage property protection
- Critical equipment
- Anti-smoking enforcement
- Motor rooms

Options Available

- Command Module available for central monitoring and display
- SenseNet compatible - up to 127 detectors per loop
- Remote Display units available
- Suitable for MatrixScan, a patented software system which provides virtual addressable location detection - e.g. 10 physical detectors would provide up to 45 unique addressable locations.

Details

  • UL approved to the latest UL268 7th edition
  • Ultra small low cost aspirating smoke detector for easy and discreet installation
  • High sensitivity provided by laser based forward light scatter for reliable early warning
  • Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
  • Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
  • RS485 communications built in as standard for networking and remote communications

Technical specifications

Electrical
Operating voltage
21.6 to 26.4 VDC
Current consumption
250 mA
Detection
Detection principle
Laser light scattering mass detection and particle evaluation
Sensitivity
0.00046% Obs/ft. to 7.62% Obs/ft. (0.0015% Obs/m to 25% Obs/m)
Particle sensitivity range
0.003μ to 10μ
Measurement range (%Obs/m) 0.0015% to 25%
Alarm levels 4 (Aux, Pre-alarm, Alarm and Alarm 2)
Physical
Physical dimensions
5.71” x 8.66” x 3.35” in (145 x 220 x 85 mm)
Net weight
3.7 lbs (1.7 kg)
Colour
Cream
Mounting type
Surface mount
Cable entries
2 x M20
Material (body)
Sheet steel enclosure
Environmental
Operating temperature
32 to +100°F (0 to +38°C) (UL)
32 to +120°F (0 to +49°C) (FM)
Relative humidity
0 to 90% noncondensing
Environment
Indoor
IP rating
IP40
Regulatory
Certification
FM
UL
Sampling pipework
Inlets 1
Diameter 27mm OD
Exhaust 1 (optional)
Outputs
Standard 2 - Alarm (n/o) and Fault (n/c)
Rating 500mA @ 30V
Expansion Optional input and relay card
User interface
Indicators LED
Networking
SenseNET (RS-485) On-board